H SERIES DIESEL GENERATOR SETS
H series diesel generator sets are driven by our H series diesel engines, jointly designed by SDEC and UK based Ricardo. The engine itself is compact and covers a wide power range with high reliability and excellent fuel efficiency. Each genset is equipped with an automatic starting device and an optional ATS switch cabinet. These components allow for automated starting and switchover between generator sets. The sets all feature high voltage regulation accuracy, dynamic performance, minimal voltage wave distortion, high efficiency, and reliability.
No | Model | Standby power(KVA) | Prime Power(KVA) | Dimension(mm) | Engine Type |
1 | SD-SC63S | 69 | 63 | 1940*940*1358 | SC4H95D2 |
2 | SD-SC80S | 88 | 80 | 1980*940*1358 | SC4H115D2 |
3 | SD-SC100S | 110 | 100 | 1985*1000*1470 | SC4H160D2 |
4 | SD-SC125S | 138 | 125 | 1985*1000*1470 | SC4H180D2 |
6 | SD-SC160S | 176 | 160 | 2400*1050*1535 | SC7H230D2 |
7 | SD-SC188S | 207 | 188 | 2400*1050*1535 | SC7H250D2 |
8 | SD-SC200S | 220 | 200 | 2540*1120*1620 | SC9D280D2 |
9 | SD-SC250S | 275 | 250 | 2700*1120*1655 | SC9D340D2 |
11 | SD-SC313S | 344 | 313 | 3220*1380*1755 | SC13G420D2 |
13 | SD-SC350S | 385 | 350 | 3220*1380*1755 | SC12E460D2 |
14 | SD-SC375S | 413 | 375 | 3200*1385*1850 | SC12E500D2 |
16 | SD-SC450S | 495 | 450 | 3550*1600*2205 | SC25G610D2 |
17 | SD-SC500S | 550 | 500 | 3570*1600*2205 | SC25G690D2 |
18 | SD-SC563S | 619 | 563 | 3570*1600*2205 | SC27G755D2 |
19 | SD-SC625S | 688 | 625 | 3570*1750*2205 | SC27G830D2 |
20 | SD-SC682S | 750 | 682 | 3570*1750*2205 | SC27G900D2 |
21 | SD-SC750S | 825 | 750 | 3800*1410*1880 | SC33W990D2 |
22 | SD-SC900S | 990 | 900 | 3800*1410*1880 | SC33W1150D2 |
* The above parameters are for reference only and subject to change without prior notice.
D SERIES DIESEL GENERATOR SETS
Shanghai New Power Automotive Technology Company Limited., AVL Powertrain Engineering (Austria), and the American Southwest Research Institute (SWRI) collaborated to develop the D series diesel engine used in the assembly of our D series diesel generator sets. The design of the engine began as a project to reinforce and upgrade older 4-valve diesel engine models. These equipment sets feature a power rating of 295kW with a margin of reliability in power range of 185-255kW. Each genset is equipped with an automatic starting device and an optional ATS switch cabinet. These components allow for automated starting and switchover between generator sets.
G SERIES DIESEL GENERATOR SETS
The G series diesel generator sets are powered by our G series in-line diesel engines which are based on the G128 Xinlong marine diesel engine. Shanghai New Power Automotive Technology Company Limited. has upgraded the original model in reliability, fuel economy, and NVH. The power generators feature outstanding voltage regulation accuracy, dynamic performance, minimal voltage wave distortion, and high efficiency. Each genset is equipped with an automatic starting device and an optional ATS switch cabinet.
W SERIES DIESEL GENERATOR SETS
The W series diesel generator sets are powered by 500-665kW W series engines. These diesel engines were specially designed by SDEC to meet high power generator set demands. The engine responds quickly to load changes and feature outstanding fuel efficiency while minimizing emissions. Thanks to their maintenance-free battery ignition system, the generator sets can be started simply by filling the fuel and coolant tanks and flipping the power switch.
E SERIES DIESEL GENERATOR SETS
Shanghai New Power Automotive Technology Company Limited. and AVL (Austria) worked alongside one another to develop the E series engine used in the assembly of our E series diesel generator sets. The E series engines are reliable, powerful, and feature fuel economy that is far superior to engines in the same power range. These generators are suitable for medium to high end generation jobs with a power range of 250-300kW.
(Voltage) | (Frequency) | ||||||
Steady-state deviation /% | Transient deviation /% | Modulation/% | Recovery time /s | Frequency drop /s | Steady-state frequency band /% | Transient deviation | Recovery time /s |
≤±2.5 | -20~+25 | 0.3 | ≤6 | ≤5 | ≤1.5 | -10~+12 | ≤5 |
Voltage range: no-load voltage regulation range is 95% - 105% of rated voltage. |
Note:
1. Unless otherwise required, the above generator sets are auto-starting type with voltage of 400 V and frequency of 50 Hz.
2. The above generator sets can be designed to feature automatic parallel operation as well as auto-starting and auto-switchover.